检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:张亚杰[1] 赵峰[2] 任淑影 张栋[2] 侯义明[1] 陈建[1] ZHANG Yajie;ZHAO Feng;REN Shuying;ZHANG Dong;HOU Yiming;CHEN Jian(Baoding Tianwei Group Tebian Electric Co.,Ltd.,Baoding 071056,China;Baoding Tianwei Baobian Electric Co.,Ltd.,Baoding 071056,China)
机构地区:[1]保定天威集团特变电气有限公司,河北保定071056 [2]保定天威保变电气股份有限公司,河北保定071056
出 处:《变压器》2025年第3期18-23,共6页Transformer
摘 要:大型单相自耦变压器常常会有半匝效应,引起变压器损耗的异常增加。本文中作者通过对一台35kV三相五柱式变压器高压绕组首末端出头不在同一侧时的理论研究与仿真和测试结果,指出当绕组首末端出头不在同一侧时应注意半匝效应对损耗的影响。Large single-phase auto-transformer often has a half-turn effect,resulting in an abnormal increase in transformer loss.Based on the theoretical research,simulation and test results of a 35kV three-phase five-column transformer,pointed out that the influence of half-turn effect on load loss should be paid attention to when the ends of the high voltage winding is not on the same side.