检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:王稼骏 张立茜 蒋治国[2,3] 周璇 费婉亲 WANG Jiajun;ZHANG Lixi;JIANG Zhiguo;ZHOU Xuan;FEI Wanqin(Zhejiang Fangyuan Electrical Equipment Testing Co.,Ltd.,Jiaxing 314001,China;School of Electronic and Information Engineering,Tongji University,Shanghai 201804,China;College of Information Science and Engineering,Jiaxing University,Jiaxing 314001,China)
机构地区:[1]浙江方圆电气设备检测有限公司,浙江嘉兴314001 [2]同济大学电子与信息工程学院,上海201804 [3]嘉兴大学信息科学与工程学院,浙江嘉兴314001
出 处:《电器与能效管理技术》2025年第1期61-67,共7页Electrical & Energy Management Technology
摘 要:为满足轨道交通、新能源等领域的中低压直流开关电器的检测需求,研制了大容量直流短路试验平台。其交流侧供电采用10 kV电网电源和短路冲击发电机双回路方案,最大短路容量达3200 MVA,最大试验能力达2 kV/350 kA及6 kV/120 kA;平台采用12脉波整流技术,直流输出信号的纹波系数<1.5%。对短时耐受电流150 kA且耐受时间200 ms的某直流断路器进行短时耐受电流试验;对额定电压1500 V、额定短路开断电流250 kA的某直流熔断器,以及最大故障条件下短路电流135/95 kA的轨道交通用直流断路器,分别进行短路分断能力试验。结果表明,试验平台能够提供满足产品需求和标准要求的试验电流、纹波系数和时间常数。To meet the testing needs of medium and low voltage DC switching device in rail transit,new energy and other fields,a large-capacity DC short-circuit test platform has been developed.The AC side power supply of the test platform adopts the optional 10 kV grid power supply and short-circuit impact generator dual-circuit option.The maximum short-circuit capacity reaches 3200 MVA,and the maximum test capability reaches 2 kV/350 kA or 6 kV/120 kA.The platform adopts twelve pulse rectification technology,and the ripple coefficient of the DC output signal is less than 1.5%.A short-time withstand current test was conducted on a DC circuit breaker with a short-time withstand current of 150 kA and a withstand time of 200 ms.Additionally,the short-circuit breaking capacity tests was seperately perfomed on a DC fuse rated at 1500 V voltage and 250 kA rated short-circuit breaking current,as well as on a DC circuit breaker designed for rail transit,which can withstand a short-circuit current of 135/95 kA under maximum fault conditions.The result show that the test platform can provide test current,ripple coefficient and time constant that meet the product needs and the standard requirements.
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.49