检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:董超群 苗亚楠 李夏 黄银龙 冯家铨 郑增辉 DONG Chaoqun;MIAO Yanan;LI Xia;HUANG Yinlong;FENG Jiaquan;ZHENG Zenghui(State Grid Henan Extra High Volatge Company,Zhengzhou 450000,China)
机构地区:[1]国网河南省电力公司超高压公司,河南郑州450000
出 处:《电工技术》2025年第2期178-180,共3页Electric Engineering
摘 要:介绍了一起500 kV变压器呼吸器漏油缺陷,对现场排查情况、缺陷原因分析、临时处理措施及停电检修过程进行了介绍。停电检查确认是储油柜胶囊破损导致变压器油流入胶囊内部,油位上升后胶囊受到挤压,油通过呼吸管出口排出,从而出现呼吸器漏油现象。最后提出了防止胶囊破损的建议,以提高胶囊的安全可靠性,保障变压器的安全运行。The article introduced the oil leakage defect of the 500 kV transformer respirator,and introduced the on-site inspection,the analysis of the causes of defects,the temporary processing measures and the power outage maintenance process.The power outage inspection confirmed that the damage to the oil storage tank capsule caused transformer oil to flow into the capsule.After the oil level rose,the capsule was compressed,and the oil was discharged from the respirator outlet through a breathing tube,resulting in respirator oil leakage.Finally,suggestions were put forward to prevent capsule damage,in order to improve the safety and reliability of the capsule and ensure the safe operation of the transformer.
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:18.116.80.77