检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:韩勇 HAN Yong
机构地区:[1]广州地铁设计研究院股份有限公司,广东广州510010
出 处:《节能》2024年第12期33-35,共3页Energy Conservation
基 金:广州地铁设计研究院股份有限公司研发课题(项目编号:KY-2022-017)。
摘 要:以常规标准地铁车站空调水系统的配置为基准,对比分析了螺杆式冷水机组、离心式冷水机组和磁悬浮离心式冷水机组在空调机房的能效表现,并计算分析了不同冷却水供回水温度对空调机房能效的影响。结果显示:当冷却水供回水温度降低至35.5/30.5℃时,制冷机房能效系数提高了约5%,这为相关设计人员在系统配置和参数选型等方面提供了参考。Based on the configuration of the conventional standard subway station air conditioning water system,the energy efficiency performance of screw chillers,centrifugal chillers,and magnetic levitation centrifugal chillers in the air conditioning room was compared and analyzed,and the influence of different cooling water supply and return temperatures on the energy efficiency of the air conditioning room was calculated and analyzed.The results show that when the cooling water supply and return water temperature is reduced to 35.5/30.5℃,the energy efficiency coefficient of the refrigeration room is increased by about 5%,which provides a reference for the relevant designers in the system configuration and parameter selection.
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:18.216.45.133