作 者:Bei YE Ge GAO Shusheng WANG Ya LI Qian JIANG 叶贝;高格;汪舒生;李亚;江钱
出 处:《Plasma Science and Technology》2025年第4期81-87,共7页等离子体科学和技术(英文版)
摘 要:This work presents a grounding protection system of the central solenoid model coil(CSMC)of the Comprehensive Research Facility for Fusion Technology(CRAFT).The scheme of neutral point voltage detections has been adopted in grounding protection system.Compared with the usual current acquisition,the measurement data is accurate,there is no redundant loop,and the economic benefit is high.In this study,the single-end and double-end grounding fault protections of superconducting magnet coil are analyzed,and the fault voltage and current under different fault conditions are calculated.The simulation model of CSMC magnet grounding fault is established,and the simulation results of the model are basically consistent with the theoretical calculation.Finally,a small capacity experiment platform is used to verify the function of the grounding protection system.The experimental results show that by comparing the neutral fault sampling voltage with the theoretical grounding protection threshold,the grounding protection system can effectively detect different types of grounding faults and transmit signals to the control system to protect the coils of superconducting magnets.
关 键 词:single-end grounding double-end grounding grounding resistance fault voltage fast discharge unit(Some figures may appear in colour only in the online journal)
分 类 号:TM8[电气工程—高电压与绝缘技术]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.62