换热站二级管网质-量调节策略及系统设计应用  

Quality-Quantity Regulation Strategy of Secondary Pipe Network and its System Design and Application in Heat Exchange Station

在线阅读下载全文

作  者:梁艳辉 Liang Yanhui(Guangzhou i-MEC Technology Co.,Ltd,Guangzhou,510000)

机构地区:[1]广州远正智能科技股份有限公司,广州510000

出  处:《制冷与空调(四川)》2025年第2期268-273,共6页Refrigeration and Air Conditioning

摘  要:针对工程应用中集中供热系统的换热站调节策略单一、参数动态调节能力不足的问题,根据热平衡方程及管网特性,提出基于室外温度与室内预设温度的供水温度调节模型和流量调节模型,并引入系数对相对负荷进行修正。在此基础上设计具备实时动态调控能力的换热站节能控制系统,并应用于换热站的实际运行控制。测试结果表明,在满足供热需求条件下,可实现二级管网热水泵节省电量30.47%,节省热量16.50%,具有良好节能效果,可为集中供热系统换热站的节能运行提供参考。This paper aims at the problems of single adjusting strategy and insufficient dynamic adjusting ability of parameters in heat exchange station of central heating system in engineering application.According to the heat balance equation and the characteristics of pipe network,the water supply temperature regulation model and flow regulation model based on outdoor temperature and indoor preset temperature are put forward,and the relative load is modified by introducing coefficient.On this basis,the energy-saving control system of heat exchange station with real-time dynamic control ability is designed applied to the actual operation control of the Heat Exchange station.Under the condition of meeting the heating demand,the test results show that the electricity of secondary network hot water pump and heat can be saved by 30.47% and 16.50% respectively.It has good energy-saving effect and can provide reference for energy-saving operation of heat exchange station in central heating system.

关 键 词:换热站 二级管网 质-量调节策略 控制系统 节能 

分 类 号:TU83[建筑科学—供热、供燃气、通风及空调工程]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象