作 者:冯玉静 赵青 姜红亮 FENG Yujing;ZHAO Qing;JIANG Hongliang
机构地区:[1]北京市煤气热力工程设计院有限公司,北京100032 [2]北京市热力集团有限责任公司研发中心,北京100023 [3]麦克维尔中央空调有限公司北京分公司,北京100023
出 处:《煤气与热力》2025年第4期9-11,共3页Gas & Heat
摘 要:结合北京地区供暖期室外温度及分时电价,制定燃气锅炉与空气源热泵耦合运行策略,以控制两种供暖设备在不同时间的启停。以严寒期典型日为例,对耦合运行与燃气锅炉单独运行的运行成本进行比较。室外温度、电价对耦合运行策略均有影响。与燃气锅炉单独运行相比,耦合运行成本下降9.38%,耦合运行成本更低。Combined with the outdoor temperature and time⁃of⁃use electricity price during the heating period in Beijing,the coupling operation strategy of gas⁃fired boiler and air⁃source heat pump was formulated to control the start and stop of the two heating equipment at different times.Taking a typical day in severe cold period as an example,the costs of coupling operation and gas⁃fired boiler standalone operation are compared.Outdoor temperature and electricity price both have an impact on the coupling operation strategy.Compared with the operation of gas⁃fired boiler alone,the cost of coupling operation is decreased by 9.38%,and the cost of coupling operation is lower.
分 类 号:TU995.7[建筑科学—供热、供燃气、通风及空调工程]