燃气厂站总图设计中规范条款和规范用词的执行  

Implementation of Standard Clauses and Terms in General Layout Design of Gas Plants and Stations

在线阅读下载全文

作  者:叶志昊 张姝媛 张红燕[2] YE Zhihao;ZHANG Shuyuan;ZHANG Hongyan

机构地区:[1]中国市政工程华北设计研究总院有限公司第十设计研究院,天津300074 [2]中国石油天然气股份有限公司规划总院,北京100083

出  处:《煤气与热力》2025年第4期V0018-V0020,共3页Gas & Heat

摘  要:在燃气厂站总图设计中,正确执行规范条款和规范用词至关重要。结合工程实例的总图设计问题,依据GB 50016—2014《建筑设计防火规范》(2018年版)第3.4.12条的条文说明,通过分析规范条款中的规范用词“不宜”,得出厂区内建筑与厂区围墙的间距视情况不同,可选择小于5 m(可以为0)、等于5 m、大于5 m或与此限值无关。In the general layout design of gas plants and stations,it is crucial to correctly implement normative clauses and terms.Combined with the general layout design issues of engineering examples and in accordance with the provisions of article 3.4.12 of Code for Fire Protection Design of Buildings(2018 edition)(GB 50016-2014),by analyzing the normative term"should not",it is found that the distance between buildings in the factory area and the factory walls varies depending on the situation,and can be selected as less than 5 meters(which can be 0),equal to 5 meters,greater than 5 meters,or unrelated to this limit.

关 键 词:不宜 建筑 围墙 条文说明 防火间距 

分 类 号:TU996.6[建筑科学—供热、供燃气、通风及空调工程]

 