过冷却水制冰蓄冷性能的实验研究  被引量:9

Experimental investigation of ice storage system with supercooling water

在线阅读下载全文

作  者:王军[1] 张定才[1] 贾丰良 

机构地区:[1]中原工学院能源与环境工程系,郑州450007 [2]河南商业设计研究所,郑州450003

出  处:《制冷学报》2002年第3期45-47,共3页Journal of Refrigeration

摘  要:利用过冷却水制冰蓄冷的关键设备是过冷却器 ,建立了过冷却器制冰蓄冷的实验装置。通过测定过冷却器进、出口两种流体的温度 ,整理绘制出正常状态下温度随时间的变化曲线。实验得出 ,当冷水温度为 - 1.5℃~1.7℃ ,流速在 1.4~ 1.8m s时 ,经管束喷出的水流会在碰撞后成冰 ,有利于制冰蓄冷 ,可得到较高的IPF值。The key equipment,on ice-storage system with supercooling water,is supercooling unit,this paper established experimental unit on ice-storage system with supercooling unit.Arrange and draw the temperature curve varied with time on normality,through measuring temperature of supercooling unit entry way and outlet of two kind of fluid.Experiment shows that the fluid water will vary ice through tube bundle after crashing,when cooling water temperatureis-1.5℃~-1.7℃ and velocity is 1.4~1.8m/s,benefit for ice-storaging,higher IPF will be received.

关 键 词:过冷却水 制冰蓄冷性能 过冷却器 HPF值 动态制冰 

分 类 号:TB657.1[一般工业技术—制冷工程]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象