检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]华中科技大学电气与电子工程学院,湖北武汉430074
出 处:《电力自动化设备》2003年第11期5-9,共5页Electric Power Automation Equipment
摘 要:基于输电线路的分布参数模型,提出利用线路两端电量的同杆平行双回线故障测距算法。根据同向正序电压故障分量沿线分布规律,使用搜索的方法确定故障距离,精确地确定各种对称、不对称跨线故障及单回线故障位置。仿真计算表明该算法测距精度高,且不要求两端数据同步,不需要判别故障类型,不存在伪根,不受线路负荷、系统阻抗和过渡电阻的影响。Based on the distributed parameter model of power transmission line,a new fault loca-ting algorithm for double-circuit line using the data of two terminals is presented.According to the distribution regularity of positive voltage's fault component along the transmission line and app-lying search method,it determines accurately the distance of fault point for various symmetric or non-symmetric inter-circuit or single-circuit faults.Furthermore,it does not require the synchronized data of two terminals and fault type identification,eliminates the influence of S/C resistance,line load and system impedance,and there is on false root.
分 类 号:TM711[电气工程—电力系统及自动化]