中央空调冷却水管腐蚀开裂失效分析  被引量:2

Corrosion fallure analysis on centrul air conditioning cooling pipe

在线阅读下载全文

作  者:陈鹭滨[1] 徐英[1] 周英勤[1] 盛伟[1] 

机构地区:[1]山东大学材料科学与工程学院,山东济南250061

出  处:《山东大学学报(工学版)》2003年第5期507-510,共4页Journal of Shandong University(Engineering Science)

摘  要:采用化学成分分析、金相检验、能谱及X射线物相分析等方法 ,对取自两地的两支中央空调冷却水管腐蚀开裂进行了分析比较 .结果表明 :冷却水中含有溶解氧及硫、氯等腐蚀性离子而缓蚀剂浓度不够是两支水管腐蚀失效的主要原因 。The corrosion cracking of two central air conditioning cooling pipe used in different region was analyzed through chemical analysis, optical microscope, and energy dispersive X-ray spectroscopy. The results show that the corrosion cracking of the cooling pipe was mainly caused by ion of oxygen, sulphur and chlorine in the cooling water and insufficiency of corrosion retardent. The rate and characteristic of corrosion cracking were also affected by the different quality of the cooling water and corrosive medium in the different region.

关 键 词:中央空调 冷却水管 点腐蚀 

分 类 号:TK122[动力工程及工程热物理—工程热物理] TQ025[动力工程及工程热物理—热能工程]

 