交流三相温升试验能用交流单相串联试验替代吗?(续)  被引量:1

Can AC Single-Phase Series Connection Supersede AC Three-phase Temperature Rise Test?

在线阅读下载全文

作  者:刘炳彰[1] 蔡璇琴[1] 林李杰 

机构地区:[1]上海电器科学研究所,上海200063 [2]乐清市飞跃开关厂,浙江乐清325604

出  处:《低压电器》2004年第3期39-44,共6页Low Voltage Apparatus

摘  要:在交流三极电器的温升试验中 ,能否用三极串联通以单相交流试验电流来替代三极中通以交流三相试验电流 ?这取决于在 2种试验方法下 ,电器各极间的电磁邻近效应是否能够忽略。本文通过理论分析和试验验证得出 :具有并联支路的三极电器 ,其温升试验不可用交流单相串联来替代交流三相。For temperature rise test method of AC three-pole apparatus, can the AC three-phase testing current passing through three-pole be superseded by series connection three-pole AC testing current passing through single-phase? It is decided by: under the two test methods, can the electromagnetic proximity effect between every pole of apparatus be ignored? This paper track theory analysis and experiment verification and came to conclusion: for the three-pole apparatus with parallel branch, its temperature rise test method of AC three-phase can not be superseded by AC single-phase series connection.

关 键 词:交流三相温升试验 交流单相串联试验 电器 电磁邻近效应 

分 类 号:TM506[电气工程—电器]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象