基于远方终端测量装置的配电网线损计算  被引量:4

Line loss calculation of 10 kV distribution network based on remote terminal measurement apparatus

在线阅读下载全文

作  者:顾秀芳[1] 刘青[2] 关长余[3] 康海珍[1] 

机构地区:[1]内蒙古工业大学电力学院,内蒙古呼和浩特010080 [2]华北电力大学,河北保定071003 [3]呼和浩特供电局,内蒙古呼和浩特010050

出  处:《继电器》2005年第11期18-21,25,共5页Relay

摘  要:当前为提高配电网自动化水平,普遍在部分线路及公用配电变压器负荷侧配置有远方终端测量装置(FTU、TTU)。这为准确计算线损提供了充实、可靠的数据来源。该文以此为出发点,将FTU、TTU采集到的三相实时数据分解为三序分量。然后对每一序网做状态估计得到整个网络的运行状态。由于状态估计不需要完全测量量,因而可大大地降低投资费用,同时使计算结果更可信。最后通过实例分析说明了此理论的可行性。Remote terminal measurement units, FTU and TTU, are commonly designed in some of lines and at load terminal of public distribution transformer to promote the level of distribution automation, which provide full and reliable data for line loss calculating precisely. This paper points out that three-phase real-time data that acquired by FTU and TTU can be resolved into three sequences of data and then state estimation can be made on each sequence of network to get the operation conditions of the whole network. Investment may be reduced greatly because that state estimation needn't full measurements. At the same time, it can make the calculation result of line loss more credible. Finally, a practical example rectifies the method is feasible.

关 键 词:配电网 线损 状态估计 FTU TTU 

分 类 号:TM744[电气工程—电力系统及自动化]

 