基于亲水/憎水复合膜的全热交换器换热换湿性能  被引量:15

Performance of heat and mass transfer based on hydrophilic/hydrophobic composite membrane

在线阅读下载全文

作  者:张炎[1] 张立志[1] 项辉[1] 徐学利[1] 

机构地区:[1]华南理工大学化工与能源学院传热强化与过程节能教育部重点实验室,广东广州510640

出  处:《化工学报》2007年第2期294-298,共5页CIESC Journal

基  金:国家自然科学基金项目(50306005);霍英东基金项目(101057);广东省自然科学基金项目(05006557)。~~

摘  要:膜全热交换器由于可以同时回收空调排风中的潜热和显热而受到重视。研究了基于PVAL/PVDF复合透湿膜的全热交换器的透热透湿性能,实验测定了新风与排风之间的显热交换能力和水蒸气交换能力,并建立了基于亲水/憎水复合膜的逆流膜全热交换器传热传质计算模型,实验与理论结果吻合较好。结果表明,该复合膜全热交换器的总传热系数为20~35W·m^-2·℃^-1,总传质系数为(1.5~3.5)×10^-3m·s^-1。The membrane-based total heat exchanger is a novel heat recovery unit due to its simultaneous recovery of sensible heat and moisture. This study investigated the heat and moisture exchange capabilities through a PVAL/PVDF composite membrane, between the fresh air and exhaust air in a total heat exchanger. A heat and mass transfer model was set up for the counter flow exchanger. The calculated and experimental results were in agreement. The total heat transfer coefficient was in the order of 20-35 W · m^-2 · ℃^-1 and the total mass transfer coefficient was in the order of (1.5-3. 5) × 10^-3 m · s^-1 respectively.

关 键 词:空调 全热交换器 复合膜 换热换湿 

分 类 号:TK124[动力工程及工程热物理—工程热物理]

 