广东电网10kV配网避雷器运行状态分析与评估  被引量:35

Running Status Analysis and Assessment of 10 kV Arresters in Guangdong Power Grid

在线阅读下载全文

作  者:彭发东[1] 彭向阳[1] 熊易[2] 雷晓燕[2] 

机构地区:[1]广东电网公司电力科学研究院,广州510080 [2]国网电力科学研究院,武汉430074

出  处:《高压电器》2011年第12期56-61,共6页High Voltage Apparatus

摘  要:介绍了目前广东电网使用的配网用避雷器的类型、安装方式,并对广东电网配网10 kV避雷器的故障模式进行详细调研统计,对现场获取的部分典型避雷器与生产厂家相同型号的未使用避雷器进行对比试验分析,分析了目前广东地区配网用避雷器的故障原因及安装和使用中存在的问题,主要为电阻片规格、密封性、结构、安装方式、接地电阻等方面不符合要求,导致广东电网配网避雷器故障较多。笔者提出应提高电阻片规格,改进密封性能、结构设计及安装方式,以提高广东电网的供电可靠性。This paper introduces the type and installation mode of 10 kV arresters in Guangdong power grid, and investigates their failure modes.Comparative tests were conducted for the failed 10 kV arresters and the new ones,and the failure causes and installation problems of the 10 kV arresters in Guangdong power grid were analyzed. The results indicate that the resistance card specification, sealing performance, structure,installation mode, and earth resistance do not meet the requirements, which leading to frequent faults with the arresters in Guangdong power grid. Some corresponding suggestions are offered to enhance the reliability of the Guangdong power grid.

关 键 词:配网 10 kV避雷器 试验研究 故障模式 

分 类 号:TM862[电气工程—高电压与绝缘技术]

 