机构地区:[1]广州地铁设计研究院有限公司 [2]广州市建筑科学研究院有限公司
出 处:《暖通空调》2015年第7期6-8,共3页Heating Ventilating & Air Conditioning
基 金:广东省教育部产学研结合项目<蒸发式冷凝地铁专用空调产品研发及应用示范>(编号:2012B091100330)
摘 要:为检验蒸发冷凝冷水机组的运行性能,对南方某地铁站车站设备管理用房冷源进行了改造,将原有2台风冷机组中的1台替换为相同冷量的蒸发冷凝冷水机组。在相同负荷、相同环境条件下对两种机组的性能和能耗进行了测试分析,发现蒸发冷凝冷水机组运行效果较优,可以达到预期的节能运行目标。In order to examine the performance of evaporative condensation water chillers,reforms the cold source of equipment management room of an underground railway station in a city of southern China.Replaces one of the two air-cooled chillers with an evaporative condensation water chiller,which has the same cooling capacity as that of the original air-cooled one. Tests the energy consumption and performances of these two kinds of chillers under the condition of the same indoor cooling load and the same outdoor temperature and humidity.The result shows that the performance of the evaporative one is higher than that of the air-cooled one,which can achieve the expected performance.