检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
机构地区:[1]上海交通大学动力与能源工程学院
出 处:《制冷与空调》2002年第4期31-35,共5页Refrigeration and Air-Conditioning
摘 要:蒸发式冷凝器设计方法的粗糙和繁琐限制其广泛应用,特别是限制其应用于民用和小型商用建筑中。针对上述问题,作者通过实验研究了蒸发式冷凝器的影响因素(进风湿球温度、最小截面风速和喷淋水量)对蒸发式冷凝器热质交换的影响。同时提出了一种新型设计方法,此方法简单,精度较高。适合工程设计、选型和生产应用。Evaporative conderser's utility was limited by its complicated designing method,in particular its usage in domestic and slight commercial unit was limited. By experimental study, the influence of the initial wet - bulb temperture of the inlet air,the air velocity passing the smallest cross area and spray water on the process of heat and mass transfer for the Evaporative londenser had been discussed by authors in this paper. Finally, the data had been regressed intoa formula. As a result ,a new designing method was made, which was simple and precise. The method was adapted to engineering design, type selection and manufature.
关 键 词:设计 蒸发式冷凝器 热质交换 淋水量 风速 “概算一校核”法 因次分析
分 类 号:TB657[一般工业技术—制冷工程]