作 者:吴俊峰 赵盼盼 张秀平 王瑜 许杨峰 Wu Junfeng;Zhao Panpan;Zhang Xiuping;Wang Yu;Xu Yangfeng(Hefei General Machinery Research Institute,Hefei 230088,China;The Chemours Chemical(Shanghai) Co.,Ltd., Shanghai 201204,China)
机构地区:[1]合肥通用机械研究院有限公司,合肥230031 [2]科慕化学(上海)有限公司,上海201204
出 处:《流体机械》2019年第7期67-71,共5页Fluid Machinery
基 金:国家重点研发计划(2016YFF0201504)
摘 要:对比分析了充注R410A和R452B的多联式空气调节机在不同工况条件下的运行参数。此外,还就制冷剂替代前后的直接排放环境效应进行了分析。结果表明:在对原机组不做任何改动,采用R452B制冷剂的机组与原R410A机组相比运行性能基本相当,减排效应良好。对比分析R410A和R452B的基本物性参数,并在R410A多联式空气调节机上开展直接充注R452B的替代试验研究。在替代前后保证机组名义制冷量基本相等(±2%误差)的条件下确定了R452B制冷剂的充注量。根据GB/T 18837-2015的工况条件测试了替代前后机组的制冷、制热以及全年性能系数的变化趋势。此外,还就制冷剂替代前后的直接排放环境效应进行了分析。结果表明,在对原机组不做任何改动,采用R452B制冷剂替代R410A制冷剂时,机组的充注量可以降低10%~15%,制冷、制热性能偏差保持在8%以内,机组的综合性能系数APF偏差保持在2%以内,CO2直接排放减排率约70%。The operating parameters of multi-connected air conditioner charged with R410 A and R452 B under different operating conditions were compared and analyzed. In addition,the environmental effect of direct emission before and after replacement of refrigerant was analyzed. The results show that the operating performance of the unit charged with refrigerant R452 B was basically equivalent to that of the unit charged with refrigerant R410 A under the condition of no modification to the original unit,and the emission reduction effect was good. The basic physical property parameters of R410 A and R452 B were compared and analyzed,and experimental study was carried out on direct replacement of refrigerant R410 A by refrigerant R452 B in the multi-connected air conditioning unit. Under the condition of ensuring that the nominal refrigerating capacity of the unit before and after replacement is basically equal (±2% error),the charge of refrigerant R452 B was determined. The change trends of cooling capacity,heating capacity and annual performance factor(APF) of the unit with different refrigerants were tested according to GB/T 18837-2015. In addition,the environmental effect of direct emission before and after replacement of refrigerant was analyzed. The results show that under the condition of no modification to the original unit,when the refrigerant R452 B was used instead of R410 A refrigerant,the refrigerant charge of the unit could be reduced by 10%~15%,the deviation of cooling and heating performance was kept within 8%,and the deviation of the integrated performance coefficient APF of the unit was kept within 2%,and the reduction rate of CO2 direct emission was about 70%.
关 键 词:R452B R410A 多联式空气调节机 性能 环境效应
分 类 号:TH12[机械工程—机械设计及理论]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:3.12.123.254