基于接地模型实测的接地装置阻抗值影响因素分析  被引量:2

Analysis of Influencing Factors of Grounding Device Impedance Based on Grounding Model Measurement

在线阅读下载全文

作  者:王琰 WANG Yan(Inner Mongolia Electric Power Research Institute,Inner Mongolia 010020,China)

机构地区:[1]内蒙古电力科学研究院,内蒙古010020

出  处:《集成电路应用》2021年第2期40-41,共2页Application of IC

基  金:内蒙古电力(集团)有限责任公司2019年科技项目(2019-36)。

摘  要:搭建了户外实体接地装置试验场,用于探索不同接地材料、不同敷设深度、不同接地面积及不同接地体长度影响条件下的接地装置阻抗情况。通过对不同接地网模型的实际测量,确认了接地阻抗值直接取决于接地体的面积,接地材料、敷设深度和接地体长度对接地装置阻抗值影响较小。The outdoor solid grounding device test field is built to explore the impedance of grounding device under the influence of different grounding materials,different laying depth,different grounding area and different grounding body length.Through the actual measurement of different grounding grid models,it is confirmed that the grounding impedance value directly depends on the area of grounding body,and the grounding material,laying depth and grounding body length have little influence on the impedance value of grounding device.

关 键 词:接地装置 阻抗值 影响因素 实际测量 接地面积 

分 类 号:TM862[电气工程—高电压与绝缘技术]

 