检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:谢宇峥 张恒旭[1] 李常刚[1] 李威 王衡 常喜强 XIE Yuzheng;ZHANG Hengxu;LI Changgang;LI Wei;WANG Heng;CHANG Xiqiang(Key Laboratory of Power System Intelligent Dispatch and Control of Ministry of Education(Shandong University),Jinan 250061,China;NARI Group Corporation(State Grid Electric Power Research Institute),Nanjing 211106,China;Electric Power Dispatching and Control Center of State Grid Xinjiang Electric Power Co.,Ltd.,Urumqi 830063,China)
机构地区:[1]电网智能化调度与控制教育部重点实验室(山东大学),山东省济南市250061 [2]南瑞集团有限公司(国网电力科学研究院有限公司),江苏省南京市211106 [3]国网新疆电力有限公司电力调度控制中心,新疆维吾尔自治区乌鲁木齐市830063
出 处:《电力系统自动化》2021年第9期153-161,共9页Automation of Electric Power Systems
基 金:国家重点研发计划资助项目(2017YFB0902600);国家电网公司科技项目(SGJS0000DKJS1700840);山东大学青年学者未来计划(2018WLJH31)的资助。
摘 要:对于可再生能源占比较高且功率通过多回高压直流大量外送的送端电网,高压直流闭锁将引发高频问题,高频切机是抑制送端电网频率升高的重要控制措施。在考虑风电机组高频保护和直流闭锁后线路有功功率变化的基础上,提出了一种高频切机方案整定方法,并将其分解为首轮单次切机总量子模型和分轮次切机量优化整定子模型。综合利用线性插值法和摄动法求解各轮次切机量,并结合二元表进行灵敏度分析,优化高频切机方案。通过中国省级电网算例验证了所提高频切机方案的有效性,并校核了所提方案在不同运行方式下的适应性。For the sending-end power grid where renewable energy accounts for a relatively high proportion and a large amount of power is sent out through multiple high-voltage direct current(HVDC)lines,HVDC blocking will cause over-frequency problems.Over-frequency generator tripping is an important control measure to restrain the frequency increase of the sending-end power grid.A setting method for the over-frequency generator tripping scheme is proposed based on considering the over-frequency protection of wind turbines and the active power change of transmission lines when HVDC blocking occurs.It is decomposed into the total generator tripping quantity submodel of the first round and the optimized setting submodel of generator tripping quantity of each basic round.The linear interpolation method and the perturbation method are used comprehensively to solve the generator tripping quantity of each round,and combined with the two-element table,the sensitivity is analyzed.Thus the over-frequency generator tripping scheme is optimized.The effectiveness of the proposed over-frequency generator tripping scheme is verified by an example of a provincial power grid in China and the adaptability of the proposed scheme is checked in different operation modes.
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.7