变压器近距故障的原因与防误措施  被引量:1

Study on Causes of Transformer Short Distance Fault and Error Prevention Measures

在线阅读下载全文

作  者:石勇 崔隽 张俊伟 SHI Yong;CUI Jun;ZHANG Junwei(NARI Group Co.,Ltd.,Jiangsu 211106,China)

机构地区:[1]南瑞集团有限公司,江苏211106

出  处:《集成电路应用》2021年第12期46-48,共3页Application of IC

摘  要:阐述外部近距离故障,产生了大量直流分量,引起微机差动保护低压侧TA直流饱和,导致比率制定和二次谐波制动失效而造成变压器差动误动的典型案例。通过实验室模拟试验,揭示误动机理,提出现场通过微机差动保护TA变化处理,从而防御区域外近距离故障时引起差动误动作。This paper expounds the typical cases of transformer differential maloperation caused by external short-range fault, resulting in a large number of DC components, causing TA DC saturation on the low-voltage side of microcomputer differential protection, resulting in ratio formulation and second harmonic braking failure. Through the laboratory simulation test, the misoperation mechanism is revealed. It is proposed to deal with the TA change of microcomputer differential protection on site, so as to prevent the differential misoperation caused by short-range fault outside the area.

关 键 词:近距离故障 微机保护 误动作 TA直流饱和 

分 类 号:TP273[自动化与计算机技术—检测技术与自动化装置] TM773[自动化与计算机技术—控制科学与工程]

 