一种适用于海上风电经MMC-MTDC并网的电网侧故障穿越方法  被引量:11

A grid-side fault ride-through method suitable for offshore wind farms connected with MMC-MTDC

在线阅读下载全文

作  者:贾科 董学正 李俊涛 李英 钮厚敏 毕天姝 JIA Ke;DONG Xuezheng;LI Juntao;LI Ying;NIU Houmin;BI Tianshu(State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources(North China Electric Power University),Beijing 102206,China)

机构地区:[1]新能源电力系统全国重点实验室(华北电力大学),北京102206

出  处:《电力系统保护与控制》2023年第21期76-85,共10页Power System Protection and Control

基  金:国家重点研发计划项目资助(2022YFB4202302)。

摘  要:海上风电工程逐渐向深远海和多端柔性直流输电技术推进。当岸上交流电网发生故障时,海上风电经多端柔直并网系统应该具有故障穿越的能力。然而现有方法主要研究电网侧换流站的系统级控制策略,未尽限利用风场侧换流站及场站内变流器的协同配合,严重故障时易导致换流站过载。此外,传统两端柔直故障穿越方法未针对多端场景改进,可能会出现风场脱网事故。针对上述问题,首先将故障划分为自消纳和非自消纳场景。自消纳场景下不平衡功率较小,结合风机自身安全减载能力和从站剩余容量,分别提出了基于降压法的超速减载和考虑功率裕度的从站电压偏差下垂控制策略。非自消纳场景下不平衡功率较大,分别提出了调度中心通信正常和异常情况下的故障穿越控制策略。最后在PSCAD/EMTDC仿真平台建模验证了所提控制方法的有效性。Offshore wind power projects are progressively expanding into deep seas and using MMC based multi-terminal direct current(MMC-MTDC).When a fault occurs on the shore AC grid side,the offshore wind farms connected to an MMC-MTDC system should have the capability of fault ride-through(FRT).However,existing methods focus on system-level control strategies between grid side converters,without considering the coordination of other converters.This oversight could lead to converter overload during severe faults.Additionally,traditional FRT methods for MMC based two-terminals have not been adapted for MTDC scenarios.This may result in wind farm disconnection.To address the above issues,faults are categorized into scenarios of self-absorption and non-self-absorption first.The unbalanced power is relatively small in the self-absorption scenario,so this paper proposes an over-speed load-shedding control strategy based on the voltage droop method and a slave station voltage deviation droop control strategy considering the power margin combining safe load-shedding capability of wind turbine itself and slave station surplus capacity.The unbalanced power is larger in the non-self-absorption scenario,so this paper proposes FRT control strategies considering normal and abnormal dispatch center communication.Finally,modeling on PSCAD/EMTDC simulation platform show the validity of the proposed control method.

关 键 词:海上风电 多端柔性直流输电 故障穿越 协同控制 不平衡功率 

分 类 号:TM721.1[电气工程—电力系统及自动化] TM614

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象